What the buyer needs
AI summaryThe government authority requires circuit switcher supplies for outdoor transmission. The equipment must be three-phase, unitized, with a control enclosure and operator.
The circuit switchers must have a 115 kilovolt nominal line voltage and be rated for 1,200 amps continuous current. They must also withstand 104,000 amps of current and have a fault closing rating of 40,000 amps.
The supplies must be SF6 gas filled, single gap puffer type interrupters with an upright design and pedestal mount. They should not include an integral disconnect switch.
Scope of work
- Three 1200AMP, 115kV outdoor transmission three-phase unitized circuit switchers
- Control enclosure and operator with 120-inch pedestal mounting height
- One complete set of approval drawings in .pdf and .dwg formats
- Two hard copy sets of final drawings and instruction manuals per cabinet
- One electronic set of final drawings, manuals, and certified test reports
Minimum qualifications
- Manufacturers must be compliant with the ISO 9000 Series
- Equipment must have a proven record of successful field operation
- Must not use equipment or parts from FCC Covered List vendors
Documents to include with your response
- Copy of ISO 9000 Series certificate
- Cut sheet or drawing and catalog number for any alternate options
- Statement on tariff applicability and Build America, Buy America compliance
- Certified factory test reports
How to submit
- Method
- Instructions
- Submit quotation via email to the buyer's procurement contact referencing RFQ 6000034345; quotes must remain valid for 90 days.